Access the Code of Practice online

This registration will be required once-only per browser/device, which is achieved using a cookie stored on your device.

There is no password required, and your information will not be shared with any third parties.

Please register and accept the terms for the NZMRM online COP
By ticking this box you confirm that you have read and accept the Terms listed below.
  • The information below will be used for our analytics ONLY.
  • No personal information will be shared with any third party.
  • Your email address will used for notifications of quarterly updates of the COP.
  • Updates may affect compliance documents.


Disclaimer

Although the information contained in this Code has been obtained from sources believed to be reliable, New Zealand Metal Roofing Manufacturers Inc. makes no warranties or representations of any kind (express or implied) regarding the accuracy, adequacy, currency or completeness of the information, or that it is suitable for the intended use.

Compliance with this Code does not guarantee immunity from breach of any statutory requirements, the New Zealand Building Code or relevant Standards. The final responsibility for the correct design and specification rests with the designer and for its satisfactory execution with the contractor.

While most data have been compiled from case histories, trade experience and testing, small changes in the environment can produce marked differences in performance. The decision to use a particular material, and in what manner, is made at your own risk. The use of a particular material and method may, therefore, need to be modified to its intended end use and environment.

New Zealand Metal Roofing Manufacturers Inc., its directors, officers or employees shall not be responsible for any direct, indirect or special loss or damage arising from, as a consequence of, use of or reliance upon any information contained in this Code.

New Zealand Metal Roofing Manufacturers Inc. expressly disclaims any liability which is based on or arises out of the information or any errors, omissions or misstatements.

If reprinted, reproduced or used in any form, the New Zealand Metal Roofing Manufacturers Inc. (NZMRM) should be acknowledged as the source of information.

You should always refer to the current online Code of Practicefor the most recent updates on information contained in this Code.

Scope

This Code of Practice provides requirements, information and guidelines, to the Building Consent Authorities, the Building Certifier, Specifier, Designer, Licensed Building Practitioner, Trade Trainee, Installer and the end user on the design, installation, performance, and transportation of all metal roof and wall cladding used in New Zealand.

The calculations and the details contained in this Code of Practice provide a means of complying with the performance provisions of the NZBC and the requirements of the Health and Safety at Work Act 2015.

The scope of this document includes all buildings covered by NZS 3604, AS/NZS 1170 and those designed and built under specific engineering design.

It has been written and compiled from proven performance and cites a standard of acceptable practice agreed between manufacturers and roofing contractors.

The drawings and requirements contained in this Code illustrate acceptable trade practice, but recommended or better trade practice is also quoted as being a preferred alternative.

Because the environment and wind categories vary throughout New Zealand, acceptable trade practice must be altered accordingly; in severe environments and high wind design load categories, the requirements of the NZBC will only be met by using specific detailing as described in this Code.

The purpose of this Code of Practice is to present both Acceptable Trade Practice and Recommended Trade Practice, in a user-friendly format to ensure that the roof and wall cladding, flashings, drainage accessories, and fastenings will:

  • comply with the requirements of B1, B2, E1 E2 and E3 of the NZBC;
  • comply with the design loading requirements of AS/NZS 1170 and NZS 3604 and with AS/NZS 1562;
  • have and optimised lifespan; and
  • be weathertight.

COP v26.09:Flashings; Flashing-Expansion-And-Contraction

8.10 Flashing Expansion and Contraction 

As flashings cannot move in the longitudinal direction without stress, they should have some provision for expansion and contraction, particularly at joints.

As aluminium rivets have limited shear strength capacity, riveted joints in flashings can be prone to “popping”. Popping happens due to timber shrinkage, thermal expansion, or a combination of the two. The best solutions to minimise the frequency and consequences of breaking joints are to attach flashings with sliding clips or to provide expansion or slip joints at appropriate spacings.

 

8.10.1 Flashing Buckling Due to Timber Shrinkage 

Transverse flashings such as head barges, ridges, and change-of-pitch flashings are particularly exposed to stress from timber shrinking as it dries. The worst can be avoided by not fixing flashings until timber moisture content is below 12%, but that is not always practical. The longitudinal shrinkage of normal radiata timber is approximately up to 3 mm per metre.

Compression timber periodically makes an appearance. Compression timber can occur in a short section of timber, which can shrink on drying up to 10 mm per metre and cause buckling of flashing and broken joints. Compression timber is hard to recognise by eye. The solutions is to wait for the timber to dry before installing flashings or, failing that, the flashings will need to be replaced once the timber moisture content has stabilised. (see 8.9 Compression Timber)

 

 

An alternative is to use steel top hat purlins, or to fix flashings using clips that allow for expansion and contraction.

8.10.2 Flashing Buckling Due to Thermal Movement 

It is necessary to make provision for thermal movement of pierce fixed flashing when long lengths are used, and end laps joints are required. To some extent the spacing of expansion joints will also depend on the accessibility of the roof for inspection and maintenance, the visibility of the joint, and the consequences of leakage through a failed joint.

Inadequate provision for expansion can also cause roof noise.

E2/AS1 requires expansion joints in steel flashings at 8 metre centres for dark coloured steel flashings, and 12 metres for light, although this is inconsistently policed. The expansion joints detailed in E2/AS1 and the old Code of Practice are 3-piece methods, that have proven unpopular with installers who consider them overly complex.

8.10.3 Recommended Expansion Joint Spacing for Flashings 

The table below is a general recommendation based on “typical” timber-framed structures. It is recommended that it as adhered to rigidly for ridges, hips, change-of-pitch flashings and head (transverse) barges. The need for expansion joints in aprons and barges is less critical and may be assessed by the installer.

Expansion joints in parapet caps are more critical than with most other flashings and will be subject to a later review.


 

8.10.3A Recommendations for Expansion Joint Spacings in Flashings

MaterialLightDark
Steel12 m8 m
Aluminium8 m6 m
Copper and Zinc6 m6 m
 

 

8.10.4 Expansion Details for Flashings 

 

 

The basic design of the details shown above can be easily translated to expansion/slip joints on other flashings such as change-of-pitch flashings and aprons. The key features are that prime fastenings do not penetrate both flashing pieces, 3 lines of sealant protection are provided, and key areas such as fastener holes and the gap between the sheet end and the roof edge are given close attention.

If rivets are required to achieve a good fit of the two flashings, these rivets should not penetrate the roof cladding. In that manner, should the rivet fail in the future, weathertight failure is avoided.

 

8.10.5 Building Expansion Joints 

Expansion joints should be designed to accommodate contraction and expansion. Expansion joints should be detailed and constructed to a minimum height of 100 mm above the roof cladding, and curb-type expansion joints should be designed and installed to ensure drainage of the roof and to prevent any damming of water.

Wood curbing secured to the substrate on both sides of an expansion joint should be flashed with a metal capping capable of acting as an expansion joint cover.

Expansion joints have two main designs.

1. A 8.10.5A One-piece Expansion Joint to accommodate movement using a central bellows or roll that allows the flashing to be positively fixed on both sides.

2. A two-piece design to accommodate movement by the use of hemmed edges, with sufficient clearance for the expected movement.

Both of these designs are shown as a parapet following the pitch of the roof. Where this is not the case, the top of flashing should have a 3 – 5˚ slope as for all other parapet flashings. (See 8.5.3 Parapet Cappings).

Metal wall construction joint flashings that are embedded in the wall should be made with a bellows or other means of accommodating movement without fatigue and have a durability of 50 years.