Underlay Standards

Permeable underlays must comply with NZS 2295, Amendment 1:2017, as shown in Properties of Roofing Underlay, or have an appropriate Product certification such as a Codemark certificate.

Reflective foil underlays must comply with AS/NZS 4200.1:2017

Minimum Requirements for Underlays for Metal Roof Cladding

Classification R1R3R2R4
Grade HeavyweightHeavyweightSelf support >/td>Self-support
Type KraftSyntheticKraft >/td>Synthetic
Application  Residential or light commercial buildings>/td> 
PropertyUnit  >/td> 
Absorbencyg/m²≥ 150≥ 150≥ 150 >/td>≥ 150
Water Vapour ResistanceMN s/g≤ 7≤ 0.5≤ 7 >/td>≤ 0.5
Water resistancemm head≥ 100≥ 100≥ 100 >/td>≥ 100
Tensile Strength MDKN/m≥ 9≥ 3≥ 11 >/td>≥ 3
Tensile Strength CDKN/m≥ 4.5≥ 2≥ 6 >/td>≥ 2.5
Edge Tear Resistance MDN≥ 40≥ 100≥ 70 >/td>≥ 150
Edge Tear Resistance CDN≥ 35≥ 80≥ 55 ≥ 130
(optional caption)

Based on Table B1 of NZS 2295 Amendment 1:2017.

  • Self-supporting (S/S) is defined as strong enough to support its own weight up to a 1200 mm span.
  • pH between 5.5 and 80.
  • Kraft based underlays shall have shrinkage less than 0.5% and maximum run-length of 10 m.
  • Synthetic underlays may have any run length.
  • Any underlay is regarded as fire-retardant if it has a Flammability Index (FI) of 5 or less when tested to AS/NZS 1530 Part 2.

 