Minimum Pitch for Generic Metal Roofing

Minimum Pitch for Generic Metal Roofing

ProfileMin HeightMin PitchCheck Capacity
after run of...
Trapezoidal
Asymmetrical
204°20 m
273°40 m
363°65 m
Trapezoidal
Symmetrical
204°15 m
303°25 m
Secret Fix303°60 m
253°30 m
Standing Seam303°85 m
253°35 m
Corrugate16.58°15 m
214°20 m
353°65 m

 

Minimum pitches quoted in this table refer to roof cladding pitch and not the building design roof pitch.
Clause Number: 
7.1.1A
/cop/roofing/roof-pitch#minimum-roof-cladding-pitch+minimum-pitch-generic-metal-roofing
Revision Category: 
2 - Editing and rearrangement
Revision Detail: 

Made corrections to some rib heights.